For a one-layer shallow water flow the Froude number is . Supercritical flow has , so both characteristic speeds point downstream. Subcritical flow has , allowing information to travel upstream. At hydraulic control the flow passes through at a geometry-induced critical section; that condition fixes discharge in relation to upstream head when the exit is free.
For escaping light air, reflect the usual lower-layer picture vertically: a lowered doorway roof acts as an inverted broad-crested weir. The lower return flow can be ignored dynamically only while it has a sufficiently large available area and small velocity. If the warm interface lies far below the doorway top, the cool inflow occupies a substantial dynamically active fraction of the opening; its inertia and pressure cannot be replaced by a motionless deep ambient. A two-layer exchange model is then required. If the warm layer reaches below the doorway bottom, the assumed separate lower replacement path is lost entirely.
Outside a freely controlled doorway the outgoing current becomes supercritical and then rises rapidly. That upturn violates the small-vertical-acceleration shallow water approximation, but it does not alter the upstream discharge as long as it does not submerge or back-pressure the control. Information cannot return through the supercritical outflow to the critical section. A blocked conservatory or a drowned doorway is different and can move the control upstream.
The room's nearly motionless upper reservoir has interface . A doorway roof at height has available light-layer head . Evaluate the Bernoulli equation in the room and at a freely controlled doorway: upstream and at its critical section. Therefore and
This is the ideal broad-crested weir law, not a small-orifice law with . A nonideal doorway would require its own measured loss correction.
When the floor heat source is on, volume conservation and buoyancy flux conservation still give and . Combine these with the doorway relation to obtain the plume-fed doorway ventilation equilibrium:
There is one interface-height root in the indicated interval. The result is physically appropriate only if its upper outflow is thin enough for the one-layer doorway model to remain valid.
If , air in the volume above the doorway is part of the upper thermal reservoir and can store heat and alter transients. But its extra depth does not add available head at the doorway: only enters the critical condition. In the steady ideal well-mixed model it shares the same density as the outflow. Treating the whole as the doorway head would overestimate discharge.
For a pure plume with , a steady sharp interface at has and warm-layer reduced gravity . A freely discharging upper doorway of height and width has available head . Equating plume supply to the broad-crested weir flux gives the displayed implicit height relation, with . Warm air above the doorway stores heat but adds no available head at its crest in this uniform-layer model.