Outside, pressure is hydrostatic with slope . Inside it has the same slope below and the shallower slope above . Thus is a negative constant below the interface, rises linearly above it with slope , and is positive at the ceiling. The floor vent admits air and the ceiling vent exhausts it.
Let be a common discharge coefficient and define the effective opening area
The ventilation flow is
Steady volume and buoyancy balances require
Therefore precisely when the effective area is chosen as
The individual areas must additionally realize this ; their ratio fixes how the total pressure drop is divided between the floor and ceiling vents.