The final state is displacement ventilation: fresh air of density forms a cool lower layer, radiator-heated air forms a well-mixed upper layer, and the wall plume crosses their interface at height . Steady volume conservation requires the plume volume flux there to equal the imposed ventilation flux,
Below the interface the ambient is uniform, so is constant. Put . The triangular-profile wall line plume equations reduce toThe pure plume conditions at the radiator select the similarity solutionConsequently the displacement-ventilation interface height isThe upper-layer reduced gravity follows from its steady buoyancy balance as . The two-layer solution applies when the calculated interface satisfies .