Electric power transmission

ID: electric-power-transmission

Electric power transmission transfers bulk electrical power between generating areas, major network junctions and receiving systems. Transmission lines carry electric current; electrical transformers change the operating electric potential difference in alternating current networks. Raising that potential can reduce the electric current required for a specified transferred power, and therefore reduce resistive heating. It also changes insulation and equipment requirements.
For an original fixed-output direct current comparison, deliver through a line with total conductor electrical resistance . At receiving-end electric potential difference , use
At , the electric current is , conductor heating is , and the source must supply at . At , the corresponding values are , and at . This compares the same receiving load and line electrical resistance; it does not assume equal source power in the two cases.
The resulting loss reduction by a factor of one hundred follows from squaring the tenfold electric current reduction. It does not imply lossless transfer: electrical transformers, converters and conductors have their own losses. The DOE treatment explicitly separates winding copper loss from useful transformer output.[ref]
Long alternating current lines also have distributed inductance and capacitance, so a resistive balance alone cannot determine their phase relationships or operating limits. An electric power transmission calculation must specify whether its electric potential differences are sending-end or receiving-end values, and whether stated power is active power or apparent power. Those conventions keep conductor-current calculations consistent with power factor.