The current-transformer ratio correction factor multiplies a nominally scaled secondary-current indication to recover primary-current magnitude under stated calibration conditions. If is the marked primary-to-secondary ratio and is the true magnitude ratio, defineNIST distinguishes this factor from ratio correction, which is , and from the separately measured phase displacement.[ref]
A Calibration Service for Current Transformers by John D. Ramboz and Oskars Petersons. §1.3, printed pp.5–6, marked/true ratio and ratio correction definitions
Correcting amplitude does not remove current-transformer phase displacement.With the inferred-primary error convention , the exact relationship isFor an original example, , and give . Using nominal scaling alone gives 498 A. The approximate correction would instead give 499.992 A, leaving a small second-order difference.
A calibration correction has its own measurement uncertainty. Treating as an exact label and retaining correlation, first-order propagation givesFor a correction inferred from uncertain , its local sensitivity is . The GUM supplies the general sensitivity-and-covariance propagation rule used here.[ref]
Nonlinearity also affects averaging. Suppose a stipulated error takes values and with equal probabilities. Its mean is zero, but the mean correction factor isThe correction at the mean error is instead one. Convexity of the reciprocal on explains this Jensen's inequality effect. It is an illustrative probability model, not a claim about random drift of a particular transformer.
A correction factor should therefore travel with its current level, frequency, current-transformer burden and uncertainty information. A proposed check repeats the ratio comparison at selected operating conditions and tests whether one retained correction remains adequate. Applying more displayed digits cannot replace that validation.