Natural ventilation Created 2026-09-28 Updated 2026-11-05
Natural ventilation exchanges air through openings using pressure differences generated by wind or buoyancy. A warmer indoor column can have a different vertical hydrostatic pressure gradient from outdoor air; connected low and high openings then permit a circulation. Wind can instead create unequal external pressures on different sides of a building.
The resulting volume flux depends on opening areas, their discharge properties and the pressure differences that remain once flow is established. The stack effect and cross ventilation describe different driving geometries and can reinforce or oppose one another. Measuring indoor/outdoor temperatures alone does not determine the exchange rate without those geometric and flow conditions. A simple thermal budget combines the exchanged enthalpy with internal heating; a stratified room can require more than one representative temperature.
The several methods are natural ventilation by wind or buoyancy, mechanical supply, mechanical extraction, and combinations of these. Each must provide both a route for clean outdoor air to enter and a route for used air to leave.
For natural ventilation, opening windows on different sides permits cross ventilation when the wind creates a suitable pressure difference. Even one window can exchange air, but the amount and distribution are more dependent on conditions. Openings at different heights use the stack effect: warmer, less dense indoor air tends to rise and leave through an upper opening, drawing replacement air through a lower one. A flue or ventilating shaft can extend this route. A fireplace may assist extraction through its chimney, provided replacement air enters and combustion products are carried safely away.
Permanent inlets, adjustable window openings and outlet shafts can make these principles more controllable. Their positions should distribute fresh air through the occupied part of the ward instead of allowing it to pass directly from inlet to outlet. An open door into an adjoining foul space is not necessarily a source of clean air. Florence Nightingale's pre-1864 discussions emphasize outside air, openings and the relation between ventilation and warmth; admitting fresh air need not mean exposing a patient to an avoidable cold draught.[ref]
Notes on Nursing by Florence Nightingale. Ventilation and warming
[ref]Notes on Hospitals by Florence Nightingale. Third edition, 1863, discussion of ward ventilation and window arrangements
With mechanical extraction, a fan or other air-moving apparatus removes indoor air, while planned inlets admit replacement air. With mechanical supply, the apparatus introduces outdoor air, and outlets allow displacement of the used air. A balanced installation provides both mechanically. Natural openings can also be combined with mechanical assistance. Heating the incoming air can reduce chilling without making it necessary to recirculate all the used air.
What matters is the actual airflow through the room, including its direction. Outlet flow can be investigated with an anemometer; short-circuiting between nearby openings and stagnant regions must be considered. Moving the same indoor air around does not by itself supply fresh air. Nor does a perfume remove a source of contamination. Source removal, sufficient exchange and reasonable temperature control belong together; windows or fans are means to those ends, not proof that they have been achieved.
Stack effect Created 2026-10-31 Updated 2026-11-05
The stack effect is buoyancy-driven flow caused by different vertical hydrostatic pressure profiles in connected columns. If indoor air is warmer and less dense than outdoor air, their pressure difference varies with height. Low and high openings can then admit cooler air below and discharge warmer air above.
For a characteristic opening separation , the driving pressure scale is , with density contrast . A small relative temperature contrast at similar absolute pressure gives in an ideal gas. This connects thermal conditions to a mechanical driving scale. The neutral pressure level marks where the two hydrostatic pressures agree, and its location depends on the connected openings and resulting flow. A larger height difference can increase the driving scale, but the final volume flux still requires opening resistance and the full circulation balance.