A controller is the rule or mechanism that chooses a control signal. An open-loop control can depend on a precomputed schedule; a feedback control also uses a measured output and can have its own memory, as in integral action.
A feedback gain sets the strength of a controller's response to its observations. For proportional control, means that a tracking error produces a control input when .
Actuator saturation means the applied control input reaches a device limit even if the controller requests a larger or smaller command. In the heater interpretation, the applied command is bounded between and . If integral action continues accumulating a persistent tracking error beyond that limit, its stored integral can grow without producing the requested physical correction, delaying recovery when the goal changes. The unconstrained steady-state tracking error formulas require that the necessary command can actually be applied. [ref]
https://www.fbswiki.org/wiki/index.php/PID_Control. Åström and Murray, PID Control: saturation and integral windup
An ideal PID controller combines proportional control, integral action, and a term proportional to the derivative of the tracking error. With , it gives proportional-integral control. The integral stores past error, while the derivative responds to its current rate of change. Practical implementations must account for measurement noise, which an ideal differentiator can amplify. [ref]
https://www.fbswiki.org/wiki/index.php/PID_Control. Åström and Murray, PID Control