Current-transformer excitation admittance represents the secondary-referred magnetic-core response as a complex ratio between current-transformer excitation current and the induced secondary electric potential difference at a stated frequency:
For a passive parallel loss-and-magnetization model, is the in-phase conductance and the inductive susceptance magnitude. NIST's equivalent circuit separates this excitation response from leakage and external current-transformer burden.[ref]
In an original linear model with parallel core-loss electrical resistance and magnetizing inductance ,
Thus and when those parameters are positive. For stipulated , and , the corresponding values are and .
At RMS, the excitation phasor is , with magnitude about . Mean power in the modeled loss branch is . The quadrature current also has physical significance even though it supplies no mean power in this ideal sinusoidal branch.
The admittance can be inferred from a measured complex transfer if the circuit assumptions are known. Let , with consistent secondary polarity, and let be winding-plus-burden impedance. The current balance gives
With the current-transformer ratio correction factor and secondary-leading phase , , so the same inversion is
Magnitude-only ratio data cannot determine both and without additional information.
A real core is nonlinear, so the effective fundamental ratio can change with excitation amplitude, frequency, waveform and magnetic history. A parameter inferred from a small perturbation about one operating state need not equal the full-signal ratio at another. NIST explicitly notes nonlinear magnetizing impedance and current/burden dependence.[ref] A proposed check measures ratio and phase at several known burdens, compares the inferred admittance values, and tests whether one local model describes them before applying it outside that range.
A current-transformer excitation current is the part of the secondary-referred input current needed for the magnetic core's response and losses rather than delivered to the external secondary circuit. In an ideal current transformer this contribution is neglected. In a real equivalent circuit it helps explain both current-transformer ratio error and current-transformer phase displacement.
Choose terminal polarities so ideal current reproduction is in phase. Let be the nominal primary-to-secondary ratio, the secondary-referred input phasor, and the measured secondary phasor. The current balance is
Represent the excitation branch locally by current-transformer excitation admittance and induced secondary phasor . With total secondary winding-plus-burden impedance ,
The NIST treatment gives the corresponding magnetizing, leakage and burden equivalent circuit and shows how those impedances enter the complex ratio.[ref]
For an original local model, write with , and take . When ,
The amplitude deficit is approximately , while the secondary lead is approximately radians. For stipulated , and , these are about and 5 milliradians. At an induced , the excitation components are 1 milliampere in phase and 5 milliamperes in quadrature; the real branch power is .
An increased current-transformer burden raises the induced potential required for a given secondary current. The actual excitation response need not remain linear: core behavior, frequency, waveform and prior magnetic state can change the local parameters. The NIST equivalent-circuit discussion explicitly notes the nonlinear core and current/burden dependence.[ref]
A proposed characterization varies a known connected burden and compares measured current ratio and phase, keeping the primary-current and frequency conditions recorded. A model that fits one operating point is not thereby validated through saturation or for arbitrary harmonic components. Separating excitation from load delivery explains why a turns ratio alone cannot specify practical measurement accuracy.
Current-transformer ratio error quantifies the amplitude mismatch between primary electric current and the value inferred by multiplying secondary current by a nominal ratio. For positive RMS magnitudes and marked primary-to-secondary ratio , define the inferred-primary fractional error as
A negative value means that nominal scaling underestimates the primary current. This explicitly states the error convention; a reported correction can have the opposite sign.
The true ratio is . The current-transformer ratio correction factor used in NIST's report convention is
NIST distinguishes marked ratio, true ratio, ratio correction and ratio correction factor in its terminology section.[ref] Error and correction are approximately negatives for small errors, but their exact fractional relationship is nonlinear.
For an original example, take , a reference primary current of , and secondary current . Nominal scaling gives , so . The correction factor is . Multiplying the nominal indication by that factor recovers 500 A; simply adding 0.4% would leave a small second-order residual.
A simplified secondary-referred equivalent circuit makes burden dependence visible. Let divide between the measured secondary current and a current-transformer excitation current. With excitation admittance and total secondary series impedance ,
This original linearized model gives amplitude error approximately and phase shift approximately when . The core response can be nonlinear; the formula is not a universal calibration curve. NIST's equivalent circuit shows the separate magnetizing, leakage and burden terms that motivate such a model.[ref]
A proposed ratio test compares primary and secondary magnitudes against a reference at stated current, frequency and current-transformer burden. Record polarity and phase separately: a correct magnitude ratio does not establish a correct active power reading. The pair of ratio and current-transformer phase displacement measurements determines the relevant complex transfer at that operating point.