John D. Ramboz is the first author, with Oskars Petersons, of NIST's 1991 account of a laboratory current transformer calibration service. The report describes ratio and phase measurements, their uncertainties and quality-control procedures for electrical measurement work.[ref] It is a primary technical record of the service and its measurement conventions.
The separation of magnitude and phase has a direct consequence for electric power measurements. Consider an original sinusoidal model with root-mean-square electric potential difference , secondary current magnitude , true current ratio and primary-current lag . True active power is
If the secondary leads the primary by , simply multiplying the secondary signal by nominal ratio gives
provided . This uses the lead-positive current-transformer phase displacement convention stated in the report.[ref]
With exact magnitude conversion and small in radians, the relative power error is approximately . For stipulated rad and , that term is about . At , its first-order value vanishes. Thus the same phase error can have different effects at different power factors.
This derivation is an explanatory example, not a reported performance test or an attribution of the calculation to Ramboz. It explains why a calibration report needs operating conditions, a sign convention and measurement uncertainty, in addition to a nominal transformer ratio. Precision in the current magnitude does not remove phase-dependent power error.