A lagging power factor describes an absorbing sinusoidal electrical load whose electric current lags its terminal electric potential difference. With the passive sign convention, choose
The current maximum occurs later by . The RMS phasors give complex electrical power
In this equation the supply phasor is the real number , while denotes the conjugate of the current phasor. Positive is inductive reactive power under this convention. The primary MIT notes derive the conjugation and the peak-versus-RMS factor.[ref]
For an original , example with , active power is and reactive power is . At , radians corresponds to a current delay of about . The factor gives the magnitude of the phase relationship, while the word lagging supplies the direction lost by the cosine.
An ideal inductor is the limiting case : it alternately stores and returns magnetic energy, with zero mean active power. An absorbing resistive-inductive load usually has both positive active power and positive reactive power. An ideal parallel capacitor can reduce the source's quadrature electric current; sufficient extra capacitance eventually crosses into leading power factor rather than improving the factor indefinitely.
For distorted waveforms, specify whether lagging refers to the fundamental displacement power factor; one phase angle does not characterize arbitrary harmonic components. A signed meter display is also not a universal lead/lag label. The manufacturer's sign-convention explanation distinguishes phase direction from the convention used for displayed factor signs.[ref]