Power factor correction changes the current drawn from a source so that a specified active power is supplied with a more favorable power factor. For a sinusoidal inductive load, a parallel capacitor can supply an opposite reactive power component. It changes the source current's quadrature component while an ideal lossless correction branch leaves the load's active power unchanged.
Let the original load absorb at RMS potential difference and angular frequency . A parallel ideal capacitance contributes , soTo change a lagging phase angle from to a smaller lagging angle at fixed ,These follow from complex electrical power and the capacitive phase relationship.[ref]
AC Power Flow in Linear Networks by James L. Kirtley Jr.. Energy and Power, equations61–65; capacitive/inductive terms in equation71
For an original ideal example, take , and50Hz. An initial factor0.8 corresponds to750var. A target factor0.95 corresponds to about328.68var, so a capacitance about33.53µF supplies the difference. RMS source current changes from6.25A to about5.26A. Resistive feeder loss at fixed resistance changes by , while the1000W load conversion remains the same in this model.
Reactive power overcompensation occurs if the capacitive contribution exceeds the intended inductive component. The net then changes sign; continuing to add capacitance does not keep improving the magnitude of the factor. At a different load or frequency the same component can produce another result. Component ratings and nonideal circuit behavior require their own model rather than being determined by this one-frequency algebra.
Correction of displacement power factor is also distinct from correction of waveform distortion. Harmonic current can remain after the fundamental quadrature component is canceled. A useful measurement compares synchronized source potential-difference/current waveforms, RMS magnitudes and their average product before and after a change, retaining the operating condition. Separately measuring only RMS magnitudes cannot establish the resulting active power.
Automatic power factor correction adjusts a correction device as the measured load changes, rather than leaving one fixed compensating setting connected. In a staged capacitor bank, a controller uses terminal electric potential difference and electric current information to choose which stages are connected. The controlled quantity and target must distinguish active power, signed reactive power, waveform distortion and the chosen lead/lag convention.
For an original single-phase sinusoidal model, available stages each supply of capacitive reactive power at the operating electric potential difference. With connected stages,At fixed , maximizing the magnitude of the power factor chooses the available integer minimizing . Away from the end limits, nearest-stage rounding leaves . This capacitor-stage quantization error can be positive or negative. A policy forbidding leading operation instead restricts , so it can choose a different setting.
Suppose , and . Three stages leave and factor about leading; two stages leave and factor about lagging. Both outcomes are consistent with their respective objectives. If the load changes to , , leaving all three stages connected produces ; zero stages is closer to cancellation than one. A stored stage decision must therefore be updated when the load changes.
Actual feedback must measure the corrected network. The Eaton paper places the current transformer so it senses the relevant load and capacitor contribution, and explains how a wrong phase, polarity or location produces misleading feedback.[ref]
Capacitor Application Issues by Thomas M. Blooming and Daniel J. Carnovale. Section VI.C, printed p.8, CT Location for Automatic Banks
Measuring only the correction branch would not establish the combined source power factor.A proposed controller test varies a known resistive-inductive load through several operating points, recording stage state, signed reactive power, RMS electric current and synchronized terminal waveforms. Check both increasing and decreasing demand, including small excursions around a stage threshold. A dead band and timing rules can prevent repeated switching in response to small fluctuations; they must be specified along with the target. Stage size, switching transients and the load's harmonic components require additional checks beyond the ideal rounding model.
Capacitor-stage quantization error is the residual reactive power caused by choosing among discrete settings of a capacitor bank instead of a continuously adjustable correction. In a fixed sinusoidal operating model, let the load absorb and let the target residual be . The desired capacitive correction is . Selecting available correction leavesThe error concerns the selected setting, separately from sensing error, changing load and component tolerance.
For equal stages of magnitude and an available range covering the desired correction, nearest-stage selection chooses an integer nearest . HenceAt a half-stage tie either neighbor attains the bound. A policy forbidding a negative residual relative to zero instead rounds downward and gives , away from the bank's capacity limits. The two policies solve different constrained problems.
For an original zero-target example, let and . Three stages give ; two give . With active power , nearest-stage selection guaranteesprovided the zero-reactive target is within range and the sinusoidal fixed-load assumptions hold. At only , the same worst-case bound falls to about . A stage size suitable at high demand need not give the same numerical power factor at low demand.
Unequal stages require the actual attainable set. Stages of 100 and 400 vars permit vars. At a desired 250 vars, the nearest setting leaves 150 vars error, despite the smallest stage being only 100 vars. The relevant bound is half the largest gap between neighboring attainable settings in the tested range, not half the smallest component. Outside the bank's range, clipping to an endpoint can leave a larger error.
At fixed frequency, a fixed capacitance gives , so stage magnitudes also change with RMS electric potential difference. Eaton's paper describes discrete stage sizes, combinations and automatic control; the error bounds above are original consequences of that ideal setting model.[ref]
Capacitor Application Issues by Thomas M. Blooming and Daniel J. Carnovale. Section V.C–D, printed p.6, stage sizes and fixed versus switched capacitors
A proposed test records the actual stage states and terminal quantities while slowly varying a known load across thresholds. Compare the observed residual with the attainable-setting prediction before assigning every deviation to quantization.Optimal shunt capacitance for sinusoidal power factor correction minimizes the source's RMS electric current for an ideal fixed sinusoidal supply and a fixed load with active power and inductive reactive power . A lossless parallel capacitor supplies signed reactive power , where is the supply RMS electric potential difference and the angular frequency.
The squared source electric current isDifferentiating givesThus the unique minimum isThe fundamental quadrature electric current vanishes there. Strict convexity proves this is a global optimum in the stated model, rather than merely a stationary point. The capacitive sign and one-frequency complex electrical power relation follow from the primary MIT derivation.[ref]
AC Power Flow in Linear Networks by James L. Kirtley Jr.. Energy and Power, equations 61–65 and 71; §7.1 RMS amplitudes
For an original example, , , and give . Source electric current falls from to . A capacitance 20% below or above leaves or , respectively, and both draw about . They have the same power factor magnitude, about , but opposite lead/lag direction.
The exact excess above the optimal squared electric current isSmall sizing errors therefore affect this loss objective quadratically around the optimum, while residual reactive power changes linearly and changes sign. An allowed interval clips the optimum to its nearest feasible point. If the original load has , the constrained optimum for added nonnegative capacitance is instead .
The result assumes a fixed load, ideal sinusoidal supply, lossless correction and no additional network effects. It does not optimize a system with waveform distortion, component heating, variable terminal electric potential difference or discrete stages. The current reduction interval for shunt reactive compensation describes a wider set of beneficial choices, while automatic power factor correction follows a changing load with available stages.
Reactive power overcompensation occurs when capacitive correction exceeds the inductive reactive power that it is intended to cancel. Under the passive sign convention and a positive-frequency sinusoidal supply, the source then sees negative net reactive power, producing a leading power factor. This can happen when a fixed capacitor bank remains connected as the inductive load falls. Eaton's application paper discusses excessive leading operation and the use of switched correction stages.[ref]
Capacitor Application Issues by Thomas M. Blooming and Daniel J. Carnovale. SectionV, printed p6, switched-bank control and overcompensation
Consider an ideal fixed RMS electric potential difference at angular frequency , supplying a load that absorbs constant and . Let be the magnitude of the correction's reactive power; its signed contribution is . Adding ideal shunt capacitance givesThe model holds the load and supply fixed while changing . It omits losses and additional network dynamics. Optimal shunt capacitance for sinusoidal power factor correction follows by minimizing the squared root mean square electric current:For the remaining reactive power is positive and the power factor is lagging. For it is negative and the power factor is leading. The overcompensation threshold is , but the current reduction interval for shunt reactive compensation is wider. Comparing the square of the corrected and uncorrected electric current givesThus source RMS current is reduced for , equals the uncorrected value at , and is larger for . An overcompensated operating point between and still draws less source electric current than the uncorrected load.
For an original example, keep the parent article's chosen , , and 50 hertz. The uncorrected source draws 6.25 amperes at power factor0.8. Full cancellation needs and reduces source electric current to 5 amperes. A 100 microfarad correction gives and 5.605 amperes, with a leading factor about0.8920. A 150 microfarad correction instead gives about and7.563 amperes, worse than no correction. The crossing is .
Leading operation begins before correction increases current above the uncorrected value
. Original constant-load model at 200 volts RMS and 50 hertz with 1000 watts active power and 750 vars inductive reactive power. Optimal correction is about 59.68 microfarads. Between 59.68 and 119.37 microfarads the source is leading but still draws less current than the uncorrected load; above 119.37 microfarads it draws more. Details.The optimum changes with the load. If the example load's and both halve while its original optimal correction remains connected, then and . Source electric current is 3.125 amperes and the factor is 0.8 leading. This dependence motivates automatic power factor correction. The cited controller description measures system electric potential difference and electric current, using external current transformers, and switches discrete capacitor bank stages to follow a target.[ref]
Retain the phase or sign of when reporting the result. A bare power factor magnitude does not distinguish leading from lagging; the manufacturer FAQ also illustrates how a meter's signed display depends on its convention.[ref]
Power factor sign conventions in Schneider Electric FAQ FA212521. Resolution and displayed IEC/IEEE convention diagrams
The calculation assumes sinusoidal steady state; current distortion factor is a separate consideration for nonsinusoidal current.The current reduction interval for shunt reactive compensation is the range of ideal capacitive corrections that draws less source RMS electric current than the uncorrected inductive load. It is wider than the range that avoids reactive power overcompensation.
Assume fixed sinusoidal RMS electric potential difference , active power , and inductive reactive power . Let be the magnitude of the added capacitive reactive power. Comparing squared source electric currents givesConsequentlyor with . The model's capacitive reactive power follows the sinusoidal complex electrical power convention.[ref]
At , source electric current is smallest. Between and , the source has a leading power factor but still draws less electric current than before correction. At , the residual reactive power is : its magnitude matches the original value, restoring the original source-current magnitude. Beyond that point the corrected electric current is larger.
For an original example, choose , and . Uncorrected electric current is . Full cancellation gives . An overcorrection leaves and draws only . But restores , and increases it to .
Two choices and are symmetric around the optimum and give the same squared source electric current. This symmetry explains why power factor magnitude alone cannot identify the sign of the residual reactive power. If , no positive reduces current under the same fixed-load assumptions.
With the same upstream electrical resistance, reducing source mean-square electric current also reduces that conductor's Joule heating. It does not erase the current carried by the local capacitor branch or assess its ratings. Harmonic interactions, nonideal components and changing load conditions need their own model; this interval is an exact statement about the stated one-frequency circuit.