AC power 2026-11-05
AC power describes energy transfer associated with time-varying electric potential difference and electric current, including the distinction between instantaneous transfer and its average. With the passive sign convention, current enters the terminal marked positive, and instantaneous power absorbed by the element is . A positive value means energy entering the element; a negative value means energy returning through that terminal pair.
For sinusoidal steady operation, choose
where and are root mean square magnitudes. The cosine-product identity gives
Averaging over a complete period removes the second term, giving active power . This derivation separates the energy-transfer average from a twice-frequency oscillation.[ref]
For an original example, , and give active power480W. The oscillating term has amplitude600W, so instantaneous power ranges from−120 to1080W. Over ten complete cycles at50Hz, the net energy absorbed is . Temporary negative power can accompany positive net transfer when an element stores and returns energy.
The product in volt-amperes is the apparent power. In the single-frequency sinusoidal convention, reactive power is , giving360 in reactive volt-amperes for a lagging current with . Complex electrical power packages and , while the power factor distinguishes net transfer from the terminal magnitude product. The primary MIT treatment derives these quantities and makes the peak-versus-RMS convention explicit.[ref]
A measurement must retain the relative phase of the two channels. Multiplying separately measured RMS magnitudes gives apparent power, not generally active power. For nonsinusoidal signals, the time average of remains the definition of active power, but one phase angle need not describe every harmonic contribution.
Active power 2026-11-05
Active power, also called real power, is the time average of instantaneous power transferred through a terminal pair. For periodic electric potential difference and electric current of common period , the passive sign convention gives
The net energy entering during each period is . Positive active power denotes net absorption under this convention; it can represent useful conversion to other forms of energy as well as heating.
For sinusoids of RMS magnitudes and with relative phase , . For a pure resistor with constant resistance , the stronger waveform-independent statement follows from :
This is why the root mean square current is the constant-current value giving the same heating in that resistor.[ref]
An original harmonic example shows why RMS values alone do not determine active power. Let
in volts and amperes. Orthogonality over a period gives , but the third harmonic averages to zero when multiplied by the fundamental potential difference. Consequently , whereas apparent power is . The power factor is0.6 even though the fundamental current is exactly in phase with the fundamental potential difference.
More generally, Fourier analysis of real periodic waveforms with RMS harmonic magnitudes gives
when the expansion and average are justified. Cross terms of different harmonic orders vanish. A single fundamental-frequency complex electrical power therefore need not capture every harmonic contribution to the total average.
For an ideal inductor or capacitor in periodic steady operation, the stored energy returns to its starting value each cycle, so its net active power is zero despite nonzero exchange during the cycle. Real components can also have losses. The primary MIT treatment explicitly separates resistor dissipation from periodic inductive and capacitive energy exchange.[ref]
Apparent power 2026-11-05
Apparent power is the product of RMS terminal electric potential difference and electric current, conventionally expressed in volt-amperes:
For sinusoidal signals at one frequency, it equals the magnitude of complex electrical power and satisfies . It is not generally the average rate of net energy absorption, which is active power.[ref]
For an original example, a100V terminal pair carrying5A RMS has500VA of apparent power. If active power is400W, the power factor is0.8. In the sinusoidal case the magnitude of reactive power is reactive volt-amperes; the magnitude calculation alone does not determine whether the current leads or lags.
Magnitudes do not add like complex quantities. Consider two parallel sinusoidal loads at the same supply, with complex powers and in volt-amperes. Each has500VA of apparent power, but the combined terminal complex power is600VA with zero imaginary part. The source therefore sees600VA rather than the1000VA sum of individual magnitudes. Their internal branch currents and individual component requirements still exist; reactive cancellation at the source does not erase those branch conditions.
For nonsinusoidal waveforms, the product definition remains useful, but the simple equality with the magnitude of one fundamental-frequency complex power needs qualification. With and , RMS current is5A and apparent power is500VA. The fundamental-frequency complex electrical power is only300VA. The extra RMS current is not represented by that one complex number.
Thus record the waveform convention with an apparent power rating or measurement. Separately measuring RMS potential difference and current gives this product, while recovering active power requires the corresponding average product or adequate phase-resolved information. The Cauchy-Schwarz inequality guarantees without assuming a sinusoidal waveform.
Complex electrical power represents the active and reactive parts of sinusoidal electrical energy transfer in one complex number. Using phasors and whose magnitudes are root mean square values, with the passive sign convention, define
The star denotes a complex conjugate. The real part is active power; the imaginary part is reactive power. The magnitude is apparent power. A source using peak-amplitude phasors instead has the factor : .[ref]
To see why the conjugate matters, write and . Then depends on the relative phase. Changing the common time reference multiplies both phasors by , leaving unchanged. The product would instead acquire and would not represent a time-reference-independent average-power quantity.
For an original example, choose and . Then
Thus active power is400W, reactive power is300 reactive volt-amperes and power factor is0.8. The corresponding electrical impedance is . With RMS current magnitude5A, the resistive term absorbs , agreeing with the real part.
Under the stated sign convention and time convention, an inductive reactance gives positive and a capacitive reactance negative . Negative does not mean a negative dissipated-energy average. For example, adding an ideal parallel capacitive branch contributing cancels this example's reactive part, leaving terminal complex power400VA and RMS source current4A at100V, while the original resistive dissipation stays400W.
This one-frequency representation must not be applied indiscriminately to a distorted waveform. Different harmonics need their own phase relationships; the definition of active power remains the time average of the actual instantaneous power.
The current reduction interval for shunt reactive compensation is the range of ideal capacitive corrections that draws less source RMS electric current than the uncorrected inductive load. It is wider than the range that avoids reactive power overcompensation.
Assume fixed sinusoidal RMS electric potential difference , active power , and inductive reactive power . Let be the magnitude of the added capacitive reactive power. Comparing squared source electric currents gives
Consequently
or with . The model's capacitive reactive power follows the sinusoidal complex electrical power convention.[ref]
At , source electric current is smallest. Between and , the source has a leading power factor but still draws less electric current than before correction. At , the residual reactive power is : its magnitude matches the original value, restoring the original source-current magnitude. Beyond that point the corrected electric current is larger.
For an original example, choose , and . Uncorrected electric current is . Full cancellation gives . An overcorrection leaves and draws only . But restores , and increases it to .
Two choices and are symmetric around the optimum and give the same squared source electric current. This symmetry explains why power factor magnitude alone cannot identify the sign of the residual reactive power. If , no positive reduces current under the same fixed-load assumptions.
With the same upstream electrical resistance, reducing source mean-square electric current also reduces that conductor's Joule heating. It does not erase the current carried by the local capacitor branch or assess its ratings. Harmonic interactions, nonideal components and changing load conditions need their own model; this interval is an exact statement about the stated one-frequency circuit.
Harmonic active power sum 2026-11-05
The harmonic active power sum expresses average electrical power as the sum of contributions from matching components of periodic terminal electric potential difference and electric current. With a common fundamental frequency and root mean square magnitudes for nonzero harmonic components, write
Here are the signed DC components. The passive sign convention makes the average product absorbed active power. Averaging over a complete fundamental period gives
For finite sums this follows from the cosine-product identity: products of different integer harmonic components average to zero, and matching components give half the cosine of their relative phase. For square-integrable periodic waveforms, the corresponding Fourier series identity follows by continuity of the inner product in the mean-square norm. The orthogonality is a property of the averaging interval and basis, not an assumption that the physical sources are independent.
For an original example, set , , , , and fundamental relative phase . Add third-harmonic magnitudes , with relative phase . Then
The third-harmonic contribution is , even though the total absorbed active power is positive. The root mean square values satisfy and , so apparent power is about and total power factor about .
For a purely sinusoidal supply with no DC component, only survives, giving even if the electric current is distorted. Current in other harmonic components can still increase conductor heating. The usual one-frequency complex electrical power construction is derived in the primary MIT treatment; the sum above applies that average-product reasoning separately to orthogonal components.[ref]
A proposed measurement records the two waveforms synchronously and compares their directly averaged product with the resolved sum. A non-integer-period window, unresolved harmonic components, channel timing error or changing waveform can spoil the simple finite-record equality. The formula assumes a shared periodic model; multiplying separately measured RMS magnitudes gives apparent power instead.
James L. Kirtley Jr. 2026-11-05
James L. Kirtley Jr. is an electrical engineer whose work concerns electric machines and electric power systems. MIT's departmental profile identifies him as a professor emeritus of electrical engineering, with energy and robotics among his research areas.[ref]
Figure 1.
James L. Kirtley Jr., portrait in MIT Energy Initiative's 2016 interview
. Identified James Kirtley photograph linked from the institutional interview; served directly by MIT.
The engineering problem is to match a motor's behaviour to its application. MIT reported in 2016 that Kirtley worked on customized electric motors for the MIT Cheetah robot, where brief peaks of torque serve running and jumping. The same interview describes his interest in electric motors interacting with microgrids, particularly their dynamic behaviour during supply disturbances.[ref] A short burst and sustained operation place different demands on the system; the largest instantaneous output alone does not describe its operating role.
His AC Power Flow in Linear Networks by James L. Kirtley Jr. connects the phasor representation of electric potential difference and electric current to physical energy transfer. In its peak-amplitude convention, complex electrical power is . With RMS phasors and , this becomes . The complex conjugate ensures that the relative phase enters the active power.[ref]
For an original load example in sinusoidal steady state, take and electrical impedance , using RMS phasors and the passive sign convention: electric current enters the positive-potential terminal. A series resistor and inductor realize this model at the specified angular frequency when and . Then
Thus active power is 48 watts, reactive power is 64 vars, apparent power is 80 volt-amperes, and power factor is . Write and . The corresponding electric potential difference and electric current are
Multiplying and applying a trigonometric identity gives instantaneous power
Its cycle average is 48 watts, while its range is watts. The negative portions represent temporary return of stored energy from this ideal load; the electrical resistance still dissipates a positive average. A synchronized product of the two waveforms reveals this behaviour, whereas multiplying their root mean square magnitudes gives only the apparent power.
Figure 2.
A phase-shifted load returns energy during part of each cycle while absorbing positive average power
. Original 20 volt RMS example with impedance ohms. The voltage and current have power factor 0.6; their instantaneous product ranges from -32 to 128 watts and averages 48 watts. Values are illustrative rather than measured motor data. Details.
Lagging power factor 2026-11-05
A lagging power factor describes an absorbing sinusoidal electrical load whose electric current lags its terminal electric potential difference. With the passive sign convention, choose
The current maximum occurs later by . The RMS phasors give complex electrical power
In this equation the supply phasor is the real number , while denotes the conjugate of the current phasor. Positive is inductive reactive power under this convention. The primary MIT notes derive the conjugation and the peak-versus-RMS factor.[ref]
For an original , example with , active power is and reactive power is . At , radians corresponds to a current delay of about . The factor gives the magnitude of the phase relationship, while the word lagging supplies the direction lost by the cosine.
An ideal inductor is the limiting case : it alternately stores and returns magnetic energy, with zero mean active power. An absorbing resistive-inductive load usually has both positive active power and positive reactive power. An ideal parallel capacitor can reduce the source's quadrature electric current; sufficient extra capacitance eventually crosses into leading power factor rather than improving the factor indefinitely.
For distorted waveforms, specify whether lagging refers to the fundamental displacement power factor; one phase angle does not characterize arbitrary harmonic components. A signed meter display is also not a universal lead/lag label. The manufacturer's sign-convention explanation distinguishes phase direction from the convention used for displayed factor signs.[ref]
Leading power factor 2026-11-05
A leading power factor describes an absorbing sinusoidal electrical load whose electric current leads its terminal electric potential difference. Under the passive sign convention, write
The current maximum occurs earlier by . The complex electrical power is
The negative reactive power is consistent with a capacitive terminal response. It does not imply negative mean absorbed active power.
For an original , example with , the power factor magnitude is , active power is , and reactive power is . At the current leads by . A load with the same RMS magnitudes and the opposite phase displacement has identical active power but a lagging power factor and opposite reactive power.
For an ideal capacitor, gives a quarter-cycle current lead. Its mean active power is zero, although instantaneous power alternates as electrical energy enters and leaves the field. The primary one-frequency power derivation separates this quadrature exchange from net energy transfer.[ref]
An inductive load can acquire a leading power factor at the source when power factor correction supplies more capacitive reactive power than the load absorbs. The current reduction interval for shunt reactive compensation shows why mildly leading operation can still draw less source electric current than no correction, while excessive correction reverses that benefit.
Record phase direction or signed reactive power together with the numerical factor. The same positive cosine can describe leading and lagging loads, and a meter may assign a separate sign according to its display convention.[ref] For nonsinusoidal signals, state whether leading describes the fundamental displacement power factor; the complete power factor also depends on waveform distortion.
Optimal shunt capacitance for sinusoidal power factor correction minimizes the source's RMS electric current for an ideal fixed sinusoidal supply and a fixed load with active power and inductive reactive power . A lossless parallel capacitor supplies signed reactive power , where is the supply RMS electric potential difference and the angular frequency.
The squared source electric current is
Differentiating gives
Thus the unique minimum is
The fundamental quadrature electric current vanishes there. Strict convexity proves this is a global optimum in the stated model, rather than merely a stationary point. The capacitive sign and one-frequency complex electrical power relation follow from the primary MIT derivation.[ref]
For an original example, , , and give . Source electric current falls from to . A capacitance 20% below or above leaves or , respectively, and both draw about . They have the same power factor magnitude, about , but opposite lead/lag direction.
The exact excess above the optimal squared electric current is
Small sizing errors therefore affect this loss objective quadratically around the optimum, while residual reactive power changes linearly and changes sign. An allowed interval clips the optimum to its nearest feasible point. If the original load has , the constrained optimum for added nonnegative capacitance is instead .
The result assumes a fixed load, ideal sinusoidal supply, lossless correction and no additional network effects. It does not optimize a system with waveform distortion, component heating, variable terminal electric potential difference or discrete stages. The current reduction interval for shunt reactive compensation describes a wider set of beneficial choices, while automatic power factor correction follows a changing load with available stages.
Power factor 2026-11-05
The power factor is the ratio of active power to the product of RMS terminal electric potential difference and electric current:
when the denominator is positive. It measures how effectively those terminal magnitudes support net average transfer. With signed absorbed power it can be negative for net generation; for an absorbing load the usual range is zero to one. The Cauchy-Schwarz inequality applied to the time average of proves .
For one-frequency sinusoids, , so the power factor is . The phase-only quantity for the fundamental is also called displacement power factor. The primary treatments make the RMS convention explicit.[ref][ref]
A distorted current can give another result. For purely sinusoidal supply potential difference and a zero-mean current with fundamental RMS magnitude ,
Only the in-phase fundamental contributes to the average product with that supply waveform. For an original example with fundamental3A in phase and third-harmonic RMS magnitude4A, total RMS current is5A. The displacement power factor is one but total power factor is0.6. Changing the fundamental phase alone would not remove this harmonic-current contribution.
At fixed absorbed active power and supply RMS potential difference, . For an original900W,230V example, changing the factor from0.6 to0.9 changes source current from about6.52 to4.35A. In the same upstream resistance, the corresponding loss becomes of its former value. This is a stipulated circuit calculation, not an assertion about a particular tariff or installation.
Power factor correction addresses the mechanism causing the low ratio. An ideal capacitive branch can offset inductive reactive power at one frequency; it does not automatically correct an arbitrary distorted current. State the waveform conditions and whether the reported number is total or displacement factor when comparing measurements.
Power factor correction 2026-11-05
Power factor correction changes the current drawn from a source so that a specified active power is supplied with a more favorable power factor. For a sinusoidal inductive load, a parallel capacitor can supply an opposite reactive power component. It changes the source current's quadrature component while an ideal lossless correction branch leaves the load's active power unchanged.
Let the original load absorb at RMS potential difference and angular frequency . A parallel ideal capacitance contributes , so
To change a lagging phase angle from to a smaller lagging angle at fixed ,
These follow from complex electrical power and the capacitive phase relationship.[ref]
For an original ideal example, take , and50Hz. An initial factor0.8 corresponds to750var. A target factor0.95 corresponds to about328.68var, so a capacitance about33.53µF supplies the difference. RMS source current changes from6.25A to about5.26A. Resistive feeder loss at fixed resistance changes by , while the1000W load conversion remains the same in this model.
Reactive power overcompensation occurs if the capacitive contribution exceeds the intended inductive component. The net then changes sign; continuing to add capacitance does not keep improving the magnitude of the factor. At a different load or frequency the same component can produce another result. Component ratings and nonideal circuit behavior require their own model rather than being determined by this one-frequency algebra.
Correction of displacement power factor is also distinct from correction of waveform distortion. Harmonic current can remain after the fundamental quadrature component is canceled. A useful measurement compares synchronized source potential-difference/current waveforms, RMS magnitudes and their average product before and after a change, retaining the operating condition. Separately measuring only RMS magnitudes cannot establish the resulting active power.
Reactive power 2026-11-05
Reactive power is the imaginary part of complex electrical power in sinusoidal steady operation. With RMS phasors, the passive sign convention and time convention,
where is potential-difference phase minus current phase. Inductive current lag gives positive , while capacitive current lead gives negative . Its conventional unit is the reactive volt-ampere, written var. These definitions retain the specified phasor and sign conventions.[ref]
The physical role is periodic energy exchange rather than an additional dissipated-energy average. For an ideal inductor, and stored energy is , so . Its energy returns to its initial value after a steady cycle and mean absorbed power is zero. Nevertheless,
For an ideal capacitor, , with the negative sign representing the opposite exchange phase. Primary circuit derivations explicitly separate these exchanges from resistor dissipation.[ref]
For an original example, , and give . Peak stored energy is0.50J and mean stored energy0.25J, consistent with . Zero ideal average dissipation therefore does not mean zero current or zero energy storage.
For a separate ideal single-frequency compensation example, a100V load with can have its source reactive component canceled by a parallel capacitor satisfying
The capacitor contributes , leaving400W of source active power and4A RMS source current. This illustrates power factor correction under the stated ideal assumptions, rather than selecting a real component or proving its ratings.
Reactive exchange can increase the current carried through resistive wiring and thereby affect real losses. For distorted waveforms, definitions of non-active power need additional care; the one-frequency imaginary-part definition should not silently be extended to every waveform.
Reactive volt-ampere 2026-11-05
The reactive volt-ampere, conventionally called the var and written with symbolvar, expresses reactive power. The official SI text notes the IEC's special name and states that its coherent unit is identical to the volt ampere. The name identifies the reactive quantity; it is not a different base-unit dimension.[ref]
In sinusoidal steady operation with RMS magnitudes and relative phase ,
Thus100V RMS,2A RMS and a lagging phase with give120var. Under the same passive and phasor conventions, a leading phase of equal magnitude gives−120var. The signed value describes exchange phase rather than negative dissipated heating. The prefix relation is .
A reactive-power value is also not an amount of stored energy in joules. For an ideal inductor in sinusoidal steady operation,
For an original200var example at50Hz, mean stored energy is and peak stored energy is twice that. The average absorbed active power is nevertheless zero in the ideal inductor. The primary circuit treatment derives this separation between energy storage and mean dissipation.[ref]
In a sinusoidal100V example with , the reactive component is300var, the active component400W and apparent power500VA. Adding400 and300 as ordinary scalar powers would not give the500VA magnitude. Complex electrical power retains the phase relation needed for this combination.
Volt-ampere 2026-11-05
The volt-ampere, symbolVA, is the unit commonly used to express apparent power. At a terminal pair, RMS potential difference in volts multiplied by RMS current in amperes gives the numerical value in volt-amperes. The unit product has the same coherent SI dimensions as the watt:
This unit identity does not make apparent power and active power the same quantity. The SI text explicitly warns that different physical quantities can share a unit and that the quantity must be specified.[ref]
For an original example,250V RMS at8A RMS gives2000VA, or2kVA. If the absorbing load has power factor0.75, its active power is1500W. A1500W value cannot be inferred from the2kVA alone without the phase/waveform information summarized by that factor.
Hypothetical equipment can have separate apparent- and active-power limits. A1000VA/600W limit would permit a500W, factor0.5 load only at the apparent-power boundary, since it requires1000VA. A700W, factor-one load would require only700VA but exceed the separate600W limit. These examples interpret stated numerical constraints rather than specify an actual product's behavior.
For single-frequency sinusoids, the magnitude of complex electrical power is expressed in volt-amperes, while its real part is commonly expressed in watts and its imaginary part in reactive volt-amperes. Those names help keep the quantities distinct even though their base-unit dimensions agree.[ref] With distorted signals, retain the actual RMS-product definition of apparent power rather than assuming a single fundamental phasor accounts for all current.