Daniel J. Carnovale 2026-11-05
Daniel J. Carnovale is an electrical engineer associated with investigating and demonstrating the behavior of electric power systems. His coauthored Capacitor Application Issues by Thomas M. Blooming and Daniel J. Carnovale identifies his Eaton affiliation; its author biography describes a demonstration and test facility for reproducing electrical supply problems and evaluating their mitigation.[ref]
One important distinction in power factor correction is between reduced source electric current and reduced useful-load active power. For an original idealized example, a load takes and at RMS. Before correction,
Canceling the fundamental reactive power makes source electric current , but leaves the stipulated load's unchanged. With a fixed upstream electrical resistance of , conductor Joule heating falls from to . The reduction is , rather than 20% of the load's active demand.
A proposed demonstration measures load active power, source RMS electric current and upstream conductor loss separately while connecting the correction branch. It makes the changed and unchanged quantities visible. The same input-output discipline applies when comparing a device's apparent electrical savings with useful service delivered. The numerical example above is an original fixed-boundary calculation, not a measurement attributed to Carnovale.
His paper with Thomas M. Blooming places such calculations within practical capacitor application. Choosing a nominal correction alone does not describe how variable load and the existing network affect operation. The distinction motivates recording terminal waveforms and operating conditions along with a single power factor number.
A distributed energy resource is a localized source or store of electrical energy connected near the consuming part of an electric power system, commonly through electric power distribution. Examples include a nearby electrical generator, an array of solar cells, and an electric battery with its power-conversion equipment. Energy storage can either absorb or deliver power; calling it a resource does not make it a net source of energy over a complete charge-discharge cycle.[ref]
For an original boundary calculation, a site consumes , its solar cells supply at the stated output boundary, and an electric battery supplies . Neglecting site losses, the imported power is
If the same electric battery instead charges at , its signed supply is and import becomes . If solar output rises to while storage is idle, the algebra gives import: an export, provided the connection and controls permit that operating point.
The location matters physically. Local generation can reduce upstream electric current when it offsets downstream consumption, but sufficiently large export can reverse the electric current. In a simplified resistive two-terminal branch, for signed electric current from supply to site; negative makes the receiving-site electric potential difference higher. This is an illustrative direct current relation, not a complete alternating current feeder calculation.
A group of distributed energy resources becomes a microgrid only with an appropriate boundary and coordinated operation. Installed generating capacity alone does not establish that disconnected operation can regulate the local supply. A useful test records import or export together with each resource's signed power, so an apparent reduction in imported energy is not confused with a change in the consuming electrical loads.
Electrical load shedding 2026-11-05
Electrical load shedding deliberately reduces connected electrical load when the available supply or operating constraints cannot support the original demand. It can disconnect selected loads or reduce their requested power. The immediate goal is a feasible remaining electric power system, with an explicit account of which service is no longer supplied.
For an original microgrid example, generation and usable storage output total , requested load is , and losses are stipulated as . At least of load must be removed in the fixed-loss model:
Suppose the optional loads are indivisible blocks of 8, 12 and 15 kilowatts. Disconnecting the 8 and 12 kilowatt blocks meets the deficit exactly, while disconnecting only the largest block does not. The choice also depends on which service must be retained; arithmetic capacity alone supplies no priority rule.
Timing matters as well as the final power balance. A deficit sustained for consumes from internal energy storage before a load action takes effect. In the rotating-machine model of electric power balance during a demand step, that draw reduces rotational kinetic energy and can reduce generated frequency. A final balanced state does not prove that the intervening trajectory stayed within operating limits.
Automatic low-frequency schemes are assessed using dynamic models, not only static subtraction. WECC's primary assessment simulated generation deficits at several load conditions and monitored frequency decline, minimum frequency and recovery. It explicitly distinguishes a simulation study from observed field response.[ref] The report's settings and scenarios are particular to that assessment, not universal instructions for another network.
A proposed small-system test imposes a known supply shortfall, records detection and disconnection times, and measures served load, source power, terminal electric potential difference and frequency through the event. Check subsequent restoration separately: reconnecting all removed loads at once can recreate the original demand step. The power-rating limit versus energy autonomy in a microgrid distinguishes a shortfall in instantaneous output from depletion over a longer interval; both can motivate different load-management decisions.
Electricity generation 2026-11-05
Electricity generation converts another form of energy into electrical energy supplied to an electrical load or electric power system. A rotating electrical generator uses electromagnetic induction; a solar cell instead converts incident radiation through the photovoltaic effect. Neither process creates energy. The relevant input and output boundaries determine which losses enter a quoted conversion fraction.
For an original ideal rotating-coil model, let turns of area rotate at constant angular velocity in a uniform magnetic field . With the coil normal initially aligned with that field, the linked magnetic flux and induced electromotive force are
For , , and , the peak is and the sinusoidal root mean square value is . Doubling the speed doubles both the amplitude and frequency in this model. The DOE exposition develops the rotating-conductor waveform and distinguishes peak from effective values.[ref]
An open-circuit induced electric potential difference does not specify deliverable power. On connecting a load, the resulting electric current produces an opposing electromagnetic torque; sustained electrical output requires corresponding mechanical input and provision for losses. For a stipulated steady shaft input of and combined losses of , output is and the shaft-to-electrical conversion fraction is . This fraction excludes any earlier conversion from fuel or another primary supply into shaft power.
A proposed demonstration couples a small electrical generator to a controllable drive, measures rotational speed and open-circuit waveform, then applies several known electrical loads while recording shaft torque, electric current and terminal electric potential difference. The additional mechanical effort under load tests the electromechanical conversion power balance; an open-circuit waveform alone cannot test that balance.
Electric power balance during a demand step tracks where the additional energy comes from when an electrical load suddenly requests more power. At an explicitly chosen system boundary, conservation of energy gives
where includes the energy storage inside that boundary. A negative right-hand side means that stored energy is decreasing. An external electric power system, an electric battery and a rotating electrical generator supply different physical buffers; they should not all be counted as independent incoming supplies if some are already included in .
For an original lumped rotating-machine example, take moment of inertia and initial angular velocity . Suppose mechanical input initially remains unchanged while electrical output increases by , with losses already accounted for. The rotational kinetic energy then obeys
After , : the extra came from rotation. This stipulated model assumes the extra delivered power can be maintained during that interval; it does not predict the load's own response to falling electric potential difference or frequency.
For a rotating electrical generator with magnetic pole pairs, the generated electrical frequency is . A speed change therefore links the energy balance to a measurable waveform change. The DOE derivation relates generated frequency to pole count and rotational speed.[ref] This rotating-machine argument does not describe every electronically controlled supply.
A proposed demand-step test records the imposed electrical load, source and storage power, terminal electric potential difference, frequency and timing of control action. The important distinction is between an initial buffer and a sustainable new operating point. If available continuous power remains too small, increasing stored energy alone does not remove that limit; electrical load shedding can instead reduce the requested output.
Electric power distribution is the part of an electric power system that delivers electrical energy from supply points to connected electrical loads. It uses conductors, switching and protective equipment, and often electrical transformers to provide suitable local electric potential differences. Electric power transmission mainly transfers bulk power between supply regions and major receiving points; the distinction concerns network function rather than one universal voltage threshold.
A one-line diagram suppresses individual phase conductors to show the supply-to-load structure. The DOE handbook's apparatus example connects utility and standby supplies, buses, switching and protection to the consuming circuits.[ref] Following the actual connection points is necessary before assigning losses or assuming that two loads share a return path.
For an original two-wire direct current example, a source holds and supplies a resistive electrical load through an outgoing-plus-return conductor electrical resistance . Ohm's law gives
The conductor heating is , while the load receives . Their sum equals the source output . Assigning the full source electric potential difference to the load would miss both its reduced terminal value and the location of the dissipated energy.
A proposed bench demonstration uses a current-limited low-voltage supply, a known series resistor representing the wires and a separate load resistor. Simultaneously measuring source and load electric potential differences and branch electric current tests the loss calculation. Real alternating current networks add electrical reactance, phase imbalance and protection constraints; the simple example isolates conductor heating rather than representing every distribution effect.
Electric power system 2026-11-05
An electric power system is an interconnected arrangement that produces, transfers, controls, and consumes electrical energy. Electricity generation supplies electrical power, electric power transmission carries it between regions, and electric power distribution delivers it to electrical loads. Electrical generators, electrical transformers, and transmission lines perform different parts of this task. The one-line apparatus diagram in the DOE handbook makes these connections concrete: it follows supplies through switching and protection equipment to consuming circuits.[ref]
A useful calculation separates delivered power from conductor heating. Consider an idealized two-conductor direct current link delivering at load electric potential difference , with total outgoing-plus-return electrical resistance . Its electric current and resistive loss are
Delivering the same power at reduces the electric current to and the loss to . This is a fixed-load, fixed-resistance comparison; it omits converter loss, insulation constraints, and changes in conductor temperature. In an alternating current network, an electrical transformer changes the operating electric potential difference without itself generating the delivered energy.[ref]
At each instant, generation, imports, and storage discharge must supply electrical load, exports, losses, and storage charging. A sudden imbalance can initially draw on stored energy; it cannot persist indefinitely without changing the operating state. This electric power balance during a demand step connects network calculations to control and to the smaller, deliberately bounded microgrid.
Islanded microgrid operation supplies a bounded set of interconnected electrical loads from its local distributed energy resources while the external electric power system connection is open. The microgrid's own equipment must then maintain a usable supply and balance demand. The DOE overview explicitly distinguishes this disconnected mode from grid-connected operation and assigns coordination and connection management to the controller.[ref]
For an original steady active power balance, local generation supplies and storage can supply at most . Connected electrical loads request and network losses are stipulated as . The shortfall is
At least of the requested demand must be removed, or more usable supply obtained, for this simplified operating point. A full electric battery does not remove the output limit. Electrical load shedding can balance the remaining demand, but it changes which service is delivered.
Passing the active power calculation is necessary but insufficient. An alternating current island must also sustain appropriate electric potential differences and frequency, accommodate reactive power, and respond to load changes. A power inverter can connect storage to the AC network, but the control capabilities and operating limits of the actual equipment determine whether it can establish or support that supply. The presence of a converter by itself proves none of those capabilities.
A proposed test records the external switch state, individual source power, storage state, load connections, electric potential differences and frequency through the transition into island operation. A load step then tests the local response described by electric power balance during a demand step. Surviving the transition and sustaining the island for a required duration are separate observations; power-rating limit versus energy autonomy in a microgrid explains why both are needed. Reconnection is another controlled operating transition, rather than simply assuming that two energized AC systems already agree in phase.
James L. Kirtley Jr. 2026-11-05
James L. Kirtley Jr. is an electrical engineer whose work concerns electric machines and electric power systems. MIT's departmental profile identifies him as a professor emeritus of electrical engineering, with energy and robotics among his research areas.[ref]
Figure 1.
James L. Kirtley Jr., portrait in MIT Energy Initiative's 2016 interview
. Identified James Kirtley photograph linked from the institutional interview; served directly by MIT.
The engineering problem is to match a motor's behaviour to its application. MIT reported in 2016 that Kirtley worked on customized electric motors for the MIT Cheetah robot, where brief peaks of torque serve running and jumping. The same interview describes his interest in electric motors interacting with microgrids, particularly their dynamic behaviour during supply disturbances.[ref] A short burst and sustained operation place different demands on the system; the largest instantaneous output alone does not describe its operating role.
His AC Power Flow in Linear Networks by James L. Kirtley Jr. connects the phasor representation of electric potential difference and electric current to physical energy transfer. In its peak-amplitude convention, complex electrical power is . With RMS phasors and , this becomes . The complex conjugate ensures that the relative phase enters the active power.[ref]
For an original load example in sinusoidal steady state, take and electrical impedance , using RMS phasors and the passive sign convention: electric current enters the positive-potential terminal. A series resistor and inductor realize this model at the specified angular frequency when and . Then
Thus active power is 48 watts, reactive power is 64 vars, apparent power is 80 volt-amperes, and power factor is . Write and . The corresponding electric potential difference and electric current are
Multiplying and applying a trigonometric identity gives instantaneous power
Its cycle average is 48 watts, while its range is watts. The negative portions represent temporary return of stored energy from this ideal load; the electrical resistance still dissipates a positive average. A synchronized product of the two waveforms reveals this behaviour, whereas multiplying their root mean square magnitudes gives only the apparent power.
Figure 2.
A phase-shifted load returns energy during part of each cycle while absorbing positive average power
. Original 20 volt RMS example with impedance ohms. The voltage and current have power factor 0.6; their instantaneous product ranges from -32 to 128 watts and averages 48 watts. Values are illustrative rather than measured motor data. Details.
Microgrid 2026-11-05
A microgrid is a bounded group of interconnected electrical loads and distributed energy resources that can be controlled as one entity. Its defining boundary and coordinated operation matter: a collection of nearby generators is not sufficient by itself. A microgrid may exchange power with an external electric power system, while islanded microgrid operation supplies its connected electrical loads without that external connection. The DOE overview identifies generation, storage, and the controller as interacting equipment, rather than treating storage capacity alone as a guarantee of service.[ref]
For a worked operating point, suppose a microgrid must supply of electrical load plus of losses. Its solar supply delivers and an electrical generator supplies . Storage must deliver
If the storage system can continuously deliver and has of usable output energy, it can support this unchanged operating point for . Here usable output energy already accounts for the chosen discharge convention; no further conversion loss is silently subtracted.
Now let a cloud reduce the solar supply to . The storage demand becomes , above its rating even with a full store. The controller must obtain more generation or reduce electrical load. This power-rating limit versus energy autonomy in a microgrid explains why an energy budget and an instantaneous power constraint must both be checked. A test of islanded microgrid operation therefore records the external connection state, generation and storage power, and the response of the connected electrical loads, rather than merely checking that a battery is present.
Thomas M. Blooming 2026-11-05
A useful technical question is why improving fundamental displacement power factor can alter the response to other harmonic components. In an original lossless parallel LC circuit, the admittance is
Its reactive terms cancel at the resonant frequency
For stipulated and , . Doubling moves it to about . A correction component chosen for one operating frequency has therefore changed the network at other frequencies as well.
In this ideal parallel model the impedance diverges at resonance; a finite imposed harmonic electric current would demand an unbounded electric potential difference, signaling the ideal model's limit. Real losses and other network elements bound and shift the response. A proposed bench test uses a small known drive and sweeps frequency with and without the extra capacitor, recording both current and potential difference. It tests the frequency-dependent circuit rather than inferring behavior from the fundamental cosine alone.
The calculation is an original illustration of the network question, not an experimental result attributed to Blooming. His joint paper with Daniel J. Carnovale supplies the application context: component choice and operating conditions must be considered together. A correction that looks favorable in a single-frequency power factor calculation is not, by that fact alone, characterized across the full waveform.